Fuel Oil Turbine Flow Meter
Light Fuel Oil & Distillate Build
Accuracy ±0.5% standard
Viscosity range ≤10 cSt at operating temperature
Light-distillate service only
- Line sizes DN4 to DN300 covering #2 heating-oil delivery, kerosene depots, distillate refinery loops, and burner-feed lines
- 316L body + 2Cr13 impeller standard for low-sulfur light fuel oil and distillate cuts
- HFO / IFO 380 / IFO 180 outside the turbine range; see Coriolis or PD options below

Light fuel oil turbines serve heating-oil dispatch, refinery distillate loops, kerosene depots, and burner-feed manifolds; No. 1/No. 2 heating oil, kerosene, distillate cuts, light cycle oil ≤10 cSt. LWGY 316L + 2Cr13 takes EN 590 trace sulfur; CNEX Ex d IIC T6 zone-1 standard. HFO/IFO 380/IFO 180 (30–380 cSt) is out of range; go to Coriolis or PD.
Benefits
- Light fuel oil only; ≤10 cSt at operating temperature
- 316L body + 2Cr13 impeller for distillate sulfur tolerance
- CNEX Ex d IIC T6 zone-1 ships standard
- ±0.5% of rate custody class; ISO 9001 cal cert
- 4-20 mA + HART, RS-485, pulse, GPRS-IoT
- 5–7 business days from the factory
Typical applications
Four light-distillate zones ≤10 cSt. HFO/residual goes to Coriolis/PD.
Residential and commercial heating-oil delivery
Tanker discharge totalizes 1–5 m³/h No. 2 heating oil for delivered-gallons invoice. Pulse drives ticketing printer; ±0.5% meets weights-and-measures.
Light-distillate burner feed for industrial boilers
Boilers fire No. 2 oil, kerosene, LCO at 10–100 m³/h day-tank-to-burner. Flow drives BMS air-fuel ratio. Ex d zone-1; ±0.5% for heat-rate.
Refinery distillate cuts and light-product transfer
Kerosene, LCO, naphtha, gas-oil on headers 50–300 m³/h, hydrotreater to blender inlet. 316L + 2Cr13 for trace-sulfur; feeds mass-balance.
Kerosene depot and aviation-jet fueling apron
Depots dispense to fuel trucks/refuelers 5–30 m³/h. Kerosene ≈1.5 cSt at 40°C; ±0.5% of rate.
Flow range by pipe size.
Volumetric flow range for No. 2 heating oil at 15 °C reference (≈840 kg/m³, ≈3 cSt) across the full LWGY Series range, DN4 to DN300. The same numbers apply to kerosene, light cycle oil, and other distillate cuts ≤10 cSt at operating temperature.
| DN | Inches | Normal range (m³/h) | Extended range (m³/h) | Connection |
|---|---|---|---|---|
| DN4 | 1/8″ | 0.04 – 0.25 | 0.04 – 0.4 | Threaded |
| DN6 | 1/4″ | 0.1 – 0.6 | 0.06 – 0.6 | Threaded |
| DN10 | 3/8″ | 0.2 – 1.2 | 0.15 – 1.5 | Threaded |
| DN15 | 1/2″ | 0.6 – 6 | 0.4 – 8 | Threaded / Flanged |
| DN20 | 3/4″ | 0.8 – 8 | 0.45 – 9 | Threaded / Flanged |
| DN25 | 1″ | 1 – 10 | 0.5 – 10 | Threaded / Flanged |
| DN32 | 1-1/4″ | 1.5 – 15 | 0.8 – 15 | Threaded / Flanged |
| DN40 | 1-1/2″ | 2 – 20 | 1 – 20 | Threaded / Flanged |
| DN50 | 2″ | 4 – 40 | 2 – 40 | Threaded / Flanged |
| DN65 | 2-1/2″ | 7 – 70 | 4 – 70 | Threaded / Flanged |
| DN80 | 3″ | 10 – 100 | 5 – 100 | Threaded / Flanged |
| DN100 | 4″ | 20 – 200 | 10 – 200 | Threaded / Flanged |
| DN125 | 5″ | 25 – 250 | 13 – 250 | Flanged |
| DN150 | 6″ | 30 – 300 | 15 – 300 | Flanged |
| DN200 | 8″ | 80 – 800 | 40 – 800 | Flanged |
| DN250 | 10″ | 125 – 1250 | 60 – 1250 | Flanged |
| DN300 | 12″ | 180 – 1800 | 90 – 1800 | Flanged |
Specifications
| Measurement principle | Velocity-type liquid turbine; torque-balance impeller cuts magnetic pickup, pulse train proportional to volumetric flow |
|---|---|
| Standard | JB/T9246-2016 turbine flow sensor |
| Applicable medium | Light fuel oil ≤10 cSt at operating temperature: No. 1 fuel oil (kerosene grade), No. 2 heating oil, No. 4 light commercial heating oil (warm), refinery distillate cuts, light cycle oil, light gas-oil. Out of scope: No. 5 / No. 6 fuel oil, HFO, IFO 380, IFO 180; use Coriolis or PD meter. |
| Pipe size range | DN4 – DN300 (1/8″ – 12″) full LWGY Series; DN4–DN15 dosing/lab, DN20–DN65 retail tanker delivery, DN50–DN150 burner feed + refinery distillate, DN150–DN300 depot transfer |
| Accuracy | ±0.5% of rate standard (custody class), ±1.0% economy build; ISO 9001 calibration certificate, K-factor verified at operating viscosity |
| Turndown | 1:10 (DN4 – DN50), 1:20 (DN65 – DN300) |
| Working pressure | 4.0 MPa (H4) standard, ANSI 150 / 300 / 600 LB flange options |
| Medium temperature | −20 to +120 °C (room-temperature type, standard) covers all light-distillate and #2 heating-oil service including warm-distillate service; −40 to +180 °C (high-temperature type) optional for cold-climate winter delivery below −20 °C; per LWGY 2-tier specification |
| Ambient temperature | −20 to +65 °C |
| Body material | 316L (code 6) standard for distillate sulfur tolerance, 304 (code 4) for kerosene low-sulfur service |
| Impeller material | 2Cr13 (code C) standard for clean light-distillate, 430F (code F) economy build |
| Connection | Threaded (DN4 – DN50, G or NPT), flanged (DN15 – DN300, ANSI 150 / 300 / 600 LB or PN 1.6 / 2.5 / 4.0 MPa) |
| Output signals | 4-20 mA (2-wire), HART (5), RS-485 Modbus-RTU (4), pulse 3-wire (2), GPRS-IoT (6) |
| Power supply | 24 V DC (U code) standard, 3.6 V lithium battery (V code) for unattended remote depots |
| Hazardous area | CNEX Ex d IIC T6 zone-1 standard for fuel-oil depot, refinery distillate loop, burner-feed manifold |
| Ingress protection | IP65 / IP66 / IP67 (IP66 typical for outdoor depot manifolds, IP67 for tanker pump-discharge stations) |
| Transmitter form | Integrated (S code) for indoor depot racks, remote (F code) for ambient-extreme or vibration-prone installations |
| Approvals | EMC 2014/30/EU (Annex II), CE, JB/T9246-2016 calibration certificate with each meter |
Installation
Five install rules, with light-fuel-oil specifics on viscosity verification, strainer selection for distillate cuts, and depot-tanker pump-discharge mounting.
- Verify operating viscosity ≤10 cSt; calibrate within ±20% of operating viscosity.
- 200-mesh Y-strainer ≥ 5D upstream; clean every 90 days on depot service.
- Mount horizontal with manual bypass loop for in-service strainer cleaning.
- 10D upstream / 5D downstream; 20D after a 90° elbow, 50D after a partial-open valve.
- Bench-test pulse pre-install; cable ≤ 1000 m, ground ≤ 10 Ω, 12-month bearing inspection.
Frequently asked questions
Need help sizing the light-fuel-oil build?
Send pipe size, fuel grade, viscosity, Ex zone, SCADA. Engineer returns DN, body/impeller, K-factor window, ballpark in 4 hours. >10 cSt or HFO/IFO goes to Coriolis/PD.