Gas Rotameter Flow Meter
Passive Visual Indication for Air, N2, O2 Lines
DN15 to DN100 metal-tube gas-calibrated float
Air reference 0.4 to 10,000 Nm³/h, ±1.5 % FS
Passive pointer (no electronics, no Ex cert) or 4-20 mA
- Magnetic float in tapered metal tube; vertical mount, flow bottom-up, gas-calibrated against air at 20 °C
- Same body covers nitrogen, oxygen, argon, dry methane with density-correction factor at order entry
- Pointer build has no electronics inside the purged volume; the working pick for NFPA 496 purge service

Metal-tube variable-area gas rotameter for compressed air, nitrogen, oxygen, and argon service. DN15 to DN100 with a gas-calibrated float (lighter than the liquid build). Reference is air at 20 °C / 101.325 kPa; N₂ / O₂ / Ar / dry methane via density-correction factor at order entry. The pointer build is passive Ex-by-design; no electronics inside the purged volume, no Ex cert burden; the pick for analyser-cabinet purge, packaged-skid drops, and shadow service alongside an electronic primary.
Benefits
- Gas-calibrated float matched to gas density: lighter than the liquid float so low-density air, N₂, O₂, and Ar rise through the calibrated scale.
- Passive Ex-by-design pointer build: no electronics, no ignition source, no Ex certificate to maintain; the pick for NFPA 496 purge service.
- ±1.5 % FS standard accuracy: factory K-factor calibrated to air at 20 °C / 101.325 kPa; density-correction factor for N₂, O₂, Ar, dry methane.
- No power required on pointer build: read the scale at 3 m without DCS, 24 VDC, or LCD; the lowest-cost gas indicator.
- DN15 to DN100 gas range: from 0.4 Nm³/h analyser-cabinet purge up to 10,000 Nm³/h packaged-skid air-drop.
- 4-20 mA / HART optional: electrical build with LCD, IP65, Ex d IIC T6 Gb when remote signal or DCS-tie is needed.
- Lead time 5–7 business days from the factory.
Configure your build.
Select your specs and the configurator returns the model code plus a ballpark unit price. Submit for engineering review and verified sizing within 4 business hours.
Your Configuration
✓ Density-correction factor applied for ordered gas
✓ Reply within 4 business hours
Typical applications
Four gas-service applications where the passive metal-tube rotameter is the working pick over an electronic primary.
N2 purge of Ex analyser cabinet
NFPA 496 Type Y / Z / X purge of classified analyser shelter. Passive pointer has no electronics inside the purged volume.
Compressed-air drop on packaged skid
Per-drop air indication on packaged plant skids. Operator reads pointer at 3 m on plant-walk; no DCS, no power, no signal chain.
O2 sub-line at industrial-gas manifold
Per-line oxygen distribution indication at industrial-gas manifold panel. Local visual confirmation at cylinder change-over.
Spot-check parallel to electronic primary
Installed alongside LWGQ turbine / CSUF ultrasonic / TMF thermal as independent visual cross-check at a fraction of unit cost.
Specifications
| Measurement principle | Variable-area; magnetic float rises in a vertically-mounted tapered metal tube; external magnetic indicator reads float position. Gas-calibrated float (lighter than liquid build) |
|---|---|
| Pipe size range | DN15, DN20, DN25, DN40, DN50, DN80, DN100 (gas service per the flow table) |
| Gas flow range (air reference) | DN15: 0.4–25 Nm³/h. DN20: 3.5–65. DN25: 7–250. DN40: 28–650. DN50: 70–1,600. DN80: 175–4,000. DN100: 450–10,000 Nm³/h (across multiple float classes) |
| Reference standard | JB/T 9248-2015 (metal-tube variable-area flow meter) |
| Compatible gases | Compressed air (post-dryer, post-oil-removal), nitrogen, oxygen, argon, dry methane; density-correction factor applied at order entry |
| Reference conditions | Air at 20 °C and 101.325 kPa (scale reference); other gases via density-correction factor |
| Accuracy | ±1.5 % FS (code A) standard; ±2.5 % FS (code B) economy |
| Repeatability | ±0.5 % FS |
| Turndown | 1:10 per float (multi-float order delivers wider effective range by float swap at re-calibration) |
| Working pressure | Up to 2.5 MPa (DN15 to DN50); up to 1.6 MPa (DN65 and above). Real-service pressure shifts indicated reading via density; specify transmitter build for pressure-compensated read |
| Medium temperature | −40 to +120 °C standard; high-T option to +220 °C; jacketed option to +300 °C |
| Ambient temperature | −40 to +65 °C |
| Wetted parts | 304 stainless steel (standard) / 316L stainless steel / Hastelloy C |
| Housing | Cast aluminium with stainless-steel measuring tube and external magnetic indicator housing |
| Indicator options | Local mechanical pointer (passive Ex-by-design, no power, no Ex cert needed) / 4-20 mA transmitter / HART / RS-485 Modbus / Hi-Lo alarm contacts |
| Display | Mechanical scale on pointer build; LCD instantaneous flow + totalizer on electrical build |
| Process connection | Flange PN16 or PN25 standard (HG/T 20592); ANSI 150 / 300 lb optional; thread NPT M20×1.5 / M36×1.5 for small-bore DN15 / DN20 |
| Form factor | Integrated (1) / remote split (2, electrical builds only) |
| Hazardous area | Passive Ex-by-design (no electronics inside the meter) on pointer build; Ex d IIC T6 Gb on electrical build |
| Ingress protection | IP65 (electrical build); IP67 / IP68 by special order |
| Power supply | None (mechanical pointer) or 24 VDC / 220 VAC (electrical) |
| Output signals | None (mechanical) / 4-20 mA / HART / RS-485 Modbus / Hi-Lo alarm contacts |
| Approvals | ISO 9001 calibration certificate with each meter; Ex d IIC T6 Gb on electrical Ex build |
| Lead time | 5–7 business days from factory |
Installation
Five install rules. Pre-condition: gas must be clean, dry, single-phase, and at known supply pressure; wet or pulsating gas service is outside the operating range.
- Vertical mount, flow bottom-up; mandatory The metal-tube rotameter relies on gravity to set the float reference; the float rises against gravity in proportion to upward flow. Plumb the body within ±2° of true vertical (spirit-level on the flange). Tilt biases the reading. Horizontal service needs a factory horizontal-build version with a different float; specify at order entry, not at install.
- Pressure compensation for gas service The float scale is calibrated to a reference pressure (typically atmospheric, air at 20 °C). Real-service pressure shifts gas density and shifts the indicated reading. For known steady supply pressure, read the scale against the published density-correction factor. For pressure-varying service, specify the electrical build with downstream temperature and pressure compensation. For billing-grade accounting, go to LWGQ turbine, LQ Roots, or CSUF ultrasonic.
- Dry the gas upstream of the meter Wet or saturated gas (compressed air pre-dryer, raw biogas, swamp gas) wets the float, biases the reading, and routes outside scope. Mount the rotameter downstream of refrigeration / desiccant dryer with at least 15 K dew-point margin. For wet or saturated gas service, go to the biogas-swirl (LUXB) counterpart.
- Avoid pulsation source upstream The float integrates over oscillation; reciprocating compressor pulsation causes pointer jitter or biased reading. Mount downstream of a pressure regulator or accumulator to smooth the inlet. Reciprocating-compressor outlet without dampener is outside the service window.
- Light straight-pipe requirement Allow ~5D upstream and ~250 mm (~2D) downstream of any disturbance; elbow, valve, reducer, tee. Lighter than turbine, but still a real requirement. Do not connect a control valve or elbow directly to the meter inlet flange. Avoid mounting near large motors or solenoid valves; external magnetic fields above ~3 mT at the indicator bias the magnetic readout.
Frequently asked questions
Need help sizing a gas indication or purge build?
Send line size, gas, supply pressure, flow range, indicator preference. Reply in 1 day; lead time 5–7 business days.