Metal Tube Rotameter Flow Meter
Passive Variable-Area Visual Indication, DN15-DN150
Accuracy ±1.5 % of full scale (class A)
304 / 316L stainless wetted parts standard
Local mechanical pointer or 4-20 mA / HART option
- Magnetic float in tapered stainless tube; vertical mount, flow bottom-up required
- Same DN body, liquid (water-ref) or gas (air-ref) calibration chosen at order
- Pointer build needs no power and no Ex certificate; electrical build is Ex d IIC T6 Gb

Variable-area metal-tube rotameter for clean liquid and gas visual indication; plant water, instrument air, sample injection, packaged-skid flow display. A magnetic float rises in a vertical tapered stainless tube; an external pointer reads float height through the wall, with no electronics in the wetted line. DN15 to DN150, 304 / 316L wetted, ±1.5 % of full scale, local pointer or 4-20 mA / HART, vertical mount. Corrosive service goes to the chemical rotameter counterpart.
Benefits
- Passive primary; no power, no electronics: the pointer build reads the magnetic float without power, transmitter, or wiring; the lowest-cost positive flow indicator on offer.
- Two display options: passive printed scale on the pointer build, or on-board LCD digital display (instantaneous flow + totalizer) on the 4-20 mA / HART electrical build.
- Vertical mount, flow bottom-up: gravity sets the float reference, so the body runs plumb with flow upward; not a field-convert.
- Viscosity bound ≤ 5 cP: standard float holds for clean low-viscosity media; heavier oils go to Coriolis or oval-gear at order entry.
- Ex-by-design pointer build: no electronics inside the body, so no Ex certificate is needed; electrical builds add Ex d IIC T6 Gb.
- Light straight-pipe demand: 5D upstream and 250 mm downstream typical; lighter than turbine, flange-to-flange package.
- Lead time 5–7 business days from the factory.
Configure your build.
Select your specs and the configurator returns the LZD model code plus a ballpark unit price. Submit for engineering review and verified sizing within 4 business hours.
Your Configuration
✓ Medium and density reviewed by application engineer
✓ Reply within 4 business hours
Typical applications
Four clean single-phase applications where the metal-tube rotameter is the visual-indication pick.
Plant water / utility lines
Cooling-water make-up, boiler feed branches, RO permeate, hose-station feed at DN25 to DN100; local pointer for operator walkthrough verification.
Instrument air and compressed gas
Post-dryer instrument-air branches, nitrogen blanket lines, oxygen distribution; gas-calibrated float reads in Nm³/h at the panel.
Sample injection and dosing
Additive metering on packaged batch skids, chemical dosing trim on RO pre-treatment, lube-oil makeup; positive visual confirmation that dosing flow is active.
OEM and skid integration
Packaged skids (RO water, lube-oil, batch additive) need a visible per-line flow indicator with no power harness; the pointer build drops in flange-to-flange.
Specifications
| Measurement principle | Variable-area; magnetic float rises in a vertical tapered metal tube; float height is a linear function of volumetric flow at calibration conditions |
|---|---|
| Pipe size range | DN15, DN20, DN25, DN32, DN40, DN50, DN65, DN80, DN100, DN125, DN150 |
| Flow range (water) | 0.025 m³/h (DN15 low-float) to 1,000 m³/h (DN150 high-float); 1:10 turndown per float, multi-float order widens effective range |
| Flow range (air) | 0.4 Nm³/h (DN15 low-float) to 10,000 Nm³/h (DN100 high-float); referenced to 20 °C, 101.325 kPa, ρ=1.205 kg/m³ |
| Accuracy | ±1.5 % of full scale (class A) / ±2.5 % of full scale (class B) |
| Turndown | 1:10 per float calibration (multi-float available for wider effective range) |
| Working pressure | Up to 2.5 MPa (DN15 to DN50); up to 1.6 MPa (DN65 to DN150); PN16 / PN25 flange standard |
| Medium temperature | −40 to +120 °C standard; +220 °C high-T build; +300 °C jacketed (steam-jacket) build |
| Ambient range | −40 to +65 °C |
| Wetted parts | 304 stainless (standard); 316L stainless option; for corrosive media see chemical rotameter counterpart |
| Float / tapered-tube material | Matches wetted-parts code; magnetic float coupling reads through the stainless wall |
| Housing | Cast aluminium with stainless measuring tube and external magnetic indicator |
| Indicator | Local mechanical pointer (passive, no power) / electrical 4-20 mA / HART transmitter / pointer + hi-lo alarm contacts |
| Output signals | 4-20 mA / HART / pulse / RS-485 Modbus / hi-lo alarm contacts (electrical build only) |
| Display | Printed scale on local pointer build; LCD instantaneous flow + totalizer on electrical build |
| Process connection | Flange PN16 / PN25 (HG/T 20592) standard; ANSI 150 / 300 lb option; NPT thread for DN15 / DN20 |
| Orientation | Vertical mount, flow bottom-up required; gravity-driven principle |
| Straight-pipe | Light demand; 5D upstream / 250 mm downstream typical |
| Power supply | 24 V DC or 220 V AC on electrical build; none on local pointer build |
| Form factor | Integrated (1) / remote split (2, electrical only) |
| Ingress protection | IP65 on electrical build; IP67 / IP68 by special order |
| Hazardous area | Ex d IIC T6 Gb on electrical build; passive (no Ex needed) on local pointer build |
| Reference standard | JB/T 9248-2015 (metal-tube variable-area flow meter), GB/T 32201-2015 industrial flow meter spec |
| Approvals | EMC 2014/30/EU on electrical build, ISO 9001 calibration certificate with each meter |
| Lead time | 5–7 business days from factory |
Installation
Five install rules. Pre-condition: meter body must run plumb vertical with flow bottom-up; the variable-area principle is gravity-driven and cannot work horizontal on a standard build.
- Vertical mount, flow bottom-up; required The float rises against gravity in proportion to upward flow drag; horizontal mount removes the gravity reference and the meter cannot return to a repeatable zero. The standard build is fixed on vertical / flow bottom-up. A horizontal-mount version exists as a separate factory build with a different float and spring assist; it is not a field-convert on a standard meter.
- Plumb the body within ±2° Confirm the meter body axis is within ±2° of true vertical with a spirit level on the flange face. Tilt biases the float reading. Pipe-stress and thermal expansion must not transfer to the meter; install proper line supports above and below, and keep short flexible runs at each flange.
- Upstream filter on clean-service builds Float-to-tube clearance is tight; particulate larger than approximately 100 µm can jam the float or scratch the bore. Install a Y-strainer or basket filter upstream sized for the line, especially on liquid service where suspended solids are possible.
- Damp pulsation upstream Variable-area meters integrate over float oscillation; reciprocating-pump or solenoid-valve pulsation causes pointer jitter and biased reading. Mount downstream of a pressure regulator or accumulator on dosing skids. Light straight-pipe demand is 5D upstream and 250 mm downstream of any disturbance (elbow, valve, reducer).
- Pointer build is passive; no Ex cert, no power harness Local mechanical pointer is the canonical low-cost / Ex-by-design choice for hazardous areas because there are no electronics inside the body. Electrical builds add Ex d IIC T6 Gb when 4-20 mA or HART output is needed. Keep large motors, solenoid banks, and magnetic strainers away from the indicator (>3 mT at the pointer biases the magnetic coupling).