Hot-Tap Water Flow Meter
Live-Pipe Retrofit on Municipal Mains
Accuracy of ±1.0% of rate
Pipe DN200 to DN3000
No service shutdown for retrofit
- Ball-valve insert under live pressure to 1.6 MPa
- 304 stainless probe with PTFE-lined 316L electrode
- Cast iron, ductile iron, cement-lined, HDPE host pipes

The Hot-Tap Water Flow Meter is the LEA-INS build for live municipal-main retrofit, DN200–DN3000. A 316L electrode probe inserts through a welded ball-valve fitting under live pressure, reading pipe-average velocity by Faraday induction.
Keeps water flowing to customers; no bypass civil works. Steel, ductile iron, cast iron, cement-lined, GRP, HDPE—non-conductive sections need a grounding ring. IP68 split-mount for buried chambers. Lead time 5–7 days.
Benefits
- No shutdown for retrofit: the ball-valve insert procedure adds measurement to a live main while continuous water service stays uninterrupted to downstream customers.
- Accuracy of ±1.0 % of rate: the calibrated single-point correction holds across 0.5 to 10 m/s for non-revenue-water audits and DMA billing.
- Cast iron, cement-lined, HDPE compatible: the probe handles legacy host pipes that an inline meter cannot replace cost-effectively.
- Wide DN range: DN200 through DN3000 covers branch sub-mains and trunk distribution on a single probe family.
- Bi-directional measurement: forward and reverse flow with separate totalizers for return-line accounting and reverse-flow leak detection.
- IP68 split-mount option: submersible probe + remote IP65 converter handles buried valve chambers and flooded distribution pits.
- Lead time: every standard configuration ships within 5–7 business days, including the welded mounting nipple and ball-valve hot-tap kit.
Typical applications
Four water-utility scenarios where hot-tap insertion EMF is the standard choice over inline meter retrofit.
DMA addition
Zone-boundary measurement on legacy cast/ductile iron mains under live pressure; non-revenue-water audits.
Trunk-main consumption metering
DN800–DN3000 trunk distribution; billing-grade flow without shipping mass or trench civil works.
Pump-station & plant outlet
DN300–DN1500 discharge/export mains; 316L probe + PTFE electrode for treated water reconciliation.
Legacy cast-iron main retrofit
Cast iron, ductile iron, cement-lined steel mains where inline replacement is not budget-feasible.
Specifications
| Measurement principle | Faraday induction with Nikuradse single-point velocity correction |
|---|---|
| Pipe size range | DN200 – DN3000 (8″ – 120″) |
| Accuracy | ±1.0 % of rate standard (calibrated 0.5 to 10 m/s) |
| Velocity range | 0 to 10 m/s (typical operation 1–3 m/s for low-noise service) |
| Conductivity threshold | ≥ 5 µS/cm (water service well above) |
| Working pressure | ≤ 1.6 MPa standard, up to 15 MPa custom on factory order |
| Medium temperature | ≤ 70 °C one-piece, ≤ 120 °C split build |
| Probe construction | 304 stainless housing, PTFE-lined electrode area, 316L stainless electrode (Hastelloy C / Ti / Ta custom on request) |
| Connection | Ball-valve insert (welded short pipe, hot-tap), large ball-valve, 1″ / 1.5″ NPT |
| Compatible host pipes | Steel, ductile iron, cast iron, cement-lined steel, GRP, HDPE, PE |
| Output signals | 4-20 mA, pulse, alarm contact, RS-485 Modbus RTU; HART / 4G IoT optional |
| Power supply | AC 110 to 245 V, DC 24 V, lithium battery option for remote AMR |
| Display | Instantaneous flow (4 digits), cumulative volume (8 digits), flow rate (4 digits) |
| Ingress protection | IP65 one-piece, IP65 + IP68 submersible split build |
| Hazardous area | CNEX Ex d IIC T6 Gb optional |
| Approvals | EMC 2014/30/EU (Annex II), ISO 9001 calibration certificate with each meter |
Installation
Five physical install rules for the hot-tap procedure on live water mains.
- Hot-tap install via ball-valve insert Weld the mounting nipple to the host pipe under prep, install the ball valve on the nipple, insert the sealed probe through the open valve under live pressure, and lock the probe at the marked insertion depth. Process pressure stays contained throughout the operation.
- Calibrated insertion depth at 1/8 D from pipe wall The probe ships pre-calibrated for the ordered DN, with the electrode placed at the Nikuradse single-point velocity location. Verify the depth lock before pressurizing. The direction marker must align with flow on every install.
- Ground probe, host pipe, and converter to ≤ 10 Ω Install a metal grounding ring on HDPE, PE, GRP, or cement-lined sections to restore the EMF ground reference. The signal cable shield grounds at the converter end only to avoid ground-loop interference on the µV-level induced EMF.
- Mount on the side or top, never the bottom on horizontal mains Side or top mounting keeps the electrode tip clear of bottom-settling sediment that accumulates on older legacy mains. On heavily silted lines, tilt the probe 45° to keep the electrode inside the active flow stream.
- Verify zero calibration with the main full and stationary at commissioning Fill the bore with the live water, stop flow at upstream and downstream isolation valves, run the zero-cal sequence, and record the baseline offset for service-life trend analysis. Re-confirm the 5D upstream / 3D downstream straight-pipe rule before pressurizing back into service.
Frequently asked questions
Need help sizing a hot-tap retrofit?
Send host DN, pipe material, pressure, buried-chamber status—sized model code, insertion depth, ship window in 5–7 business days.