Spool Piece Ultrasonic Flow Meter (2-Channel)
Drop-In Pre-Fabricated Spool, Factory-Calibrated as a Sealed Unit
±0.5 % at 0.5 to 5 m/s, repeatability 0.15 %
24 V DC, 5 W. IP54 transmitter, IP68 wetted transducer
Modbus RTU, 4-20 mA, OCT (open-collector) pulse, relay
- Two-path geometry fixed inside the spool piece; no field commissioning of multi-path alignment.
- One calibration record covers the whole sealed unit, useful for OEM custody-skid certification.
- Inline only on this model; for split-body wall-mount 2-channel, go to the field-installed multi-path model.

The Spool Piece Ultrasonic Flow Meter (2-Channel) ships as a pre-fabricated short pipe segment with the transducers built in. Two paths cross the bore on offset planes; the firmware averages their velocities. The whole spool is factory-calibrated as a sealed unit; multi-path geometry is fixed at the factory, no field alignment needed. DN25 to DN5000, ±0.5 % at 0.5 to 5 m/s. Inline drop-in only. Modbus RTU, 4-20 mA, OCT pulse, relay. 24 V DC. 5–7 business days.
Benefits
- Factory cal as a sealed unit; no field alignment. Two-path geometry fixed inside the spool at the factory. Drop-in between flanges; follow install rules to keep the calibration trace valid.
- Single calibration record covers the whole spool. Useful for OEM custody-skid certification and audit-trail reporting where multiple in-line components would each need their own commissioning trace.
- ±0.5 % across DN25 to DN5000. Velocity 0.5 to 5 m/s. Linearity ±0.5 %, repeatability 0.15 %. Two-path averaging absorbs the velocity-profile asymmetry that biases single-path readings.
- Optional PT100 pair returns kWh / MJ / BTU. PT100 sensors mount externally on supply / return pipework, factory-cal’d separately. Transmitter combines spool flow with PT100 ΔT for energy output on 4-20 mA and Modbus.
- Modbus RTU + 4-20 mA + OCT pulse + relay. 24 V DC, 5 W. Response 500 ms. Pre-configured slave address ships with each meter.
Configure your build.
Build a model code from DN, BTU option, output, and power. Send the code with the application and flange spec. Engineering replies with a sized quote within one business day.
Your configuration
Applications
OEM custody-skid drop-in
White-label custody skid for utility chargeback or industrial allocation. Drop-in spool removes field commissioning risk; one calibration trace covers the whole unit.
Trunk-line primary metering
DN500 to DN5000 utility primary distribution. Two-path averaging holds ±0.5 % on large bore; sealed-unit factory cal removes commissioning uncertainty.
Fiscal sub-meter with audit trail
Tenant billing or internal allocation where the spool ships with a single full-unit calibration trace. Suits installs where field-built multi-path commissioning is impractical.
District-heat substation (with BTU)
Substation primary entry. Optional PT100 pair (external, on supply/return pipework) adds kWh / MJ / BTU on the same transmitter. Drop-in spool fits substation skids.
Full specifications.
| Measurement principle | 2-channel transit-time ultrasonic; two acoustic chord paths on offset planes; firmware averages the two path velocities to estimate the cross-section mean velocity |
|---|---|
| Channels | 2 acoustic paths |
| Body form | Pre-fabricated short pipe segment (spool); transducers built in at the factory; calibrated as a sealed unit before shipment |
| Nominal diameter | DN25 to DN5000 |
| Accuracy | ±0.5 % of reading at velocity 0.5 to 5 m/s |
| Linearity | ±0.5 % |
| Repeatability | 0.15 % |
| Velocity range | 0.1 to 12 m/s operating; accuracy spec ±0.5 % within 0.5 to 5 m/s |
| Response time | 500 ms |
| Install style | Inline drop-in spool between flanges (C8 form); no wall-mount split-body version on this model; go to the field-installed Multi-Path 2-Channel for W8 split-body |
| Optional BTU pair | PT100 supply + return pair (mounted externally on the supply and return pipework, factory-cal’d separately); transmitter combines spool flow with PT100 ΔT to solve E = integral of (m-dot x Cp x delta-T) dt; output kWh / MJ / BTU selectable on display and on the 4-20 mA energy-rate channel |
| Output; analog | 4-20 mA, max load 600 ohm |
| Output; digital | RS-485 Modbus RTU |
| Output; other | OCT (open-collector) pulse + high / low alarm; relay 30 V DC at 1 A, switching frequency under 2 Hz |
| Display | LCD 2.8-inch IPS, 320 × 240 resolution, 4-direction rotation; unit selection m³/h, LPM, mL/min, GPM, LPH |
| Power | 24 V DC, 5 W |
| Medium | Single-phase liquid, 100 % pipe-fill; water, aqueous solution, chemical reagent; suspended solids 4 % or less |
| Medium temperature | −40 to +80 deg C (sensor head) |
| Ambient temperature | −40 to +60 deg C transmitter; −40 to +80 deg C sensor head |
| Ingress protection | IP54 transmitter housing; IP68 wetted transducer head |
| Process connection | Flange ANSI B16.5 / EN 1092-1 / GB/T 9119 (specify at order with face-to-face length) |
| Hazardous area | Not declared on this model; route Ex-classified service to clamp-on or insertion ultrasonic model with CNEX Ex d IIC certificate |
| Compliance ships standard | Full-spool calibration record with each meter (serial number, tested flow range, sealed-unit calibration trace); notified-body custody-transfer certificate is buyer-arranged |
| Lead time | 5–7 business days from factory |
Installation rules.
Spool drop-in is straightforward but five rules keep the calibration trace valid.
- Bolt the spool between flanges with the flow arrow pointing downstream. Reverse install voids the calibration trace until field re-check.
- 5D upstream, 3D downstream straight-pipe (D = pipe diameter). Hold 10D after pumps or out-of-plane double elbows.
- Pipe must stay 100 % liquid-filled. Air pockets falsify the transit-time signal on both paths. Closed loops need a vent on the loop high point.
- Torque flange bolts evenly per the flange-spec table. Uneven torque distorts the spool geometry and the factory calibration drifts.
- Verify the Modbus slave address at commissioning. Factory pre-configures from the BMS or DCS spec; field edits via the front-panel menu.